綜自變電站常見故障淺析
盧海平 王冶
摘要:斷路器作為輸變電設備的主要開關設備,它的正常運行與否關系著整個電網的安全穩定可靠運行。近年來,隨著科技的發展,輸變電站設備自動化水平越來越高。對斷路器的運行維護和檢修人員也提出了更高的技術水平要求。本文作者通過總結歷年來的工作經驗,結合工作中遇到的實際案例,舉一反三對斷路器可能出現的故障和故障原因,判斷方法和解決措施進行了詳細說明。 關鍵字:綜合自動化;變電站;斷路器;故障 Abstract: the circuit breaker as the main switch equipment transformation equipment, its normal operation or not relates to the whole of the safe and stable and reliable operation of the power grid. In recent years, with the development of science and technology, automation level transformation station equipment is getting higher and higher. The operation and maintenance of circuit breaker repair and maintenance personnel also put forward higher technical level requirements. The author summarizes the work experience, combining over real cases work across to breaker may appear, acquire the faults and fault reasons, judging methods and measures for a detailed explanation. Key word: integrated automation substation breaker failure 隨著科技的進步、社會的發展,電網結構更加堅強合理,變電站綜合自動化水平越來越高,對于出現故障后如何沉著果斷應對,才能迅速控制故障范圍,消除故障的根源,使變電站電氣設備安全、可靠、經濟運行呢,我現針對綜自變電站斷路器常見問題進行以下簡要分析: 1 斷路器合閘失靈分析 斷路器合閘失靈,是常出現的事故之一,值班人員若處理不當,往往拖延送電時間。因此。應迅速根據操作過程中的異常現象。初步判斷故障范圍和原因,進行必要的故障排除,及時恢復對用電的供電。 1.1 斷路器合閘失靈的原因 1.1.1 遠方或就地控制開關與操作方式不對應; 1.1.2 儲能(合閘)電源空氣開關在分閘位置或接觸不良,合閘電源回路不通; 1.1.3 控制電源開關在分閘位置或接觸不良,控制回路不通;(控故障) 1.1.4 合閘操作回路元件(輔助開關接觸不良或未接通);(控故障) 1.1.5 合閘線圈損壞;(控故障) 1.1.6 斷路器本體內部卡滯; 1.1.7 彈簧機構未儲能或儲能不到位;(控故障) 1.1.8 機械部分卡滯; 1.2 一般處理步驟 1.2.1 首先,合閘失靈后,發現斷路器沒有合上,應立即斷開控制電源,防止合閘線圈損壞; 1.2.2 判明是否屬操作不當; 1.2.3 檢查合閘電源、控制電源是否正常,直流電壓是否正常范圍以內,彈簧儲能情況,紅、綠燈指示情況,人為調整后合閘送電; 1.2.4 以上情況正常,根據合閘鐵芯動作與否,判明故障范圍(電氣回路和機械回路); 1.2.5 對于能短時間內自行查明并處理的故障,采取相應的措施處理,立即合閘送電; 1.2.6 對于不能處理的問題應查明故障類型,及時匯報上級及調度,由檢修人員進行處理。 2 斷路器跳閘失靈的處理 斷路器跳閘失靈,在發生事故時會造成母線失壓(越級跳閘)使事故擴大,甚至系統瓦解,并且由于依靠上一級電源的后備保護動作跳閘,即擴大了事故范圍又延長了切除故障的時間,嚴重破壞了系統的穩定性,加大了設備的損壞程度。
斷路器跳閘失靈分以下幾種情況: 2.1 運行中的斷路器發生事故保護拒動或保護動作,但斷路器拒跳:(后果) 2.1.1 越級跳閘; 2.1.2 擴大事故范圍; 2.1.3 延長了切除故障時間; 2.1.4 破壞系統穩定性; 2.1.5 加大了設備損壞程度。